logo

Plug - in LHR

Plug in Halogen free rigid conduit. For electrical instalations acording to UNE EN 61386-2-2

  • No dangerous toxic and corrosive gases are produced
  • Very little smoke gas is generated.
  • Escape routes can be found more quickly.

Standard

Class code 4433
UNE EN 50267-1/2-3 Corrosive gasses Non corrosive
UNE EN 60695-2-4 Flame propagation Non flame propagating
UNE-EN 61386 Compressive strength 1.250 N
UNE-EN 61386-1 Impact strength (-5ºC) 6 J
UNE 60423 Dimensional Yes
UNE-EN 61386-1 Temperature -15ºC / 105ºC

 

Dimensions

Diameter16202532405063
mmOutside

16

20

25

32

40

50

63
Inside 11.5 15.4 19.9 26.3 33.9 42.8 53
Package (m) 57 57 57 30 30 15 15
Length (m) 3 3 3 3 3 3 3